Filling sequence
The Tracker 244 and 225 have 2 relays with volt free contact or 4 TTL outputs respectively. These outputs can be used for alarms or for a batch control filling sequence.
The filling modes can be "Fill", where the container to be filled is on the load cells, or "Loss of weight" where the product's reservoir/tank is on the load cells.
Typical Fill Control Sequence
This sequence will detect a new empty container is in position and will fill to 97Kg (Setpoint 1 / Output 1) and then trickle feed to 100Kg (Setpoint 2 / Output 2) to avoid over filling.
- Start Trigger - detects the weight of a empty container (Optionally triggered by a logic input or front panel push button)
- Wait Predetermined time (seconds)
- Tare Load cell value
- Zero and start cut-off Timer (Pre-set maximum fill time)*
- Switch Outputs 1 and 2 on (Fill and Trickle feed valves open)
- Wait until 97Kg is measured or cut-off timer pre set time exceeded*
- Turn Off Output 1 and 2
- Wait Pre set in-flight time
- Store actual weight (e.g. 97.35Kg)**
- Turn on output 2 (trickle feed valve open only)
- Wait until 100Kg delivered or cut-off timer exceeded*
- Turn off Output 2
- Wait in-flight time
- Store weight value (e.g. 100.12Kg)**
* The sequence will be terminated immediately if the cut-off time is exceeded.
** The actual fill weights are stored to calculate the in-flight setpoint ajustments for the next sequence to improve filling accuracy.